Use this checklist after physical installation is complete to verify the system is fully operational.
Pre-power
All breakers securely mounted on DIN rail
All power wiring terminals tightened to recommended torque: 2.5 Nm for breakers rated below 63A, 3 Nm for breakers rated 63-80A
Power wiring (phase, neutral, earth) correctly terminated
RS485 daisy chain complete - controller through all breakers using supplied wire (rated 110°C / 600V)
RS485 polarity (A/B) consistent at every point
Edge Controller mounted, network cable ready
PSU connected to protected 230V AC supply
UPS connected if fitted (3.7V / 20Ah Li-Polymer)
Enclosure rated for calculated heat load
Note on the RS485 daisy chain: this step has no equivalent in a conventional panel · standard breakers need no communication wiring. Every Hybird breaker must be connected into the chain. If you have not done this step before, watch this short video of an installer connecting the RS485 wires between breakers:
If the video does not display above, watch the daisy-chaining video on Loom.
Power on
PSU outputting 24V DC
Controller green power LED illuminated
Breaker LEDs blinking a single work-mode colour: red (breaker ON) or blue (breaker OFF) · the LED always blinks, never solid
No breaker LED alternating between two colours with purple in the pattern (blinking blue/purple or blinking purple/red = setup mode, dip switch down) unless addressing is in progress
No immediate breaker trips when circuits are energised
This is what a correctly commissioned breaker looks like after power on · blinking red, dip switch up in work mode, handles up:
If the video does not display above, watch the work-mode video on Loom. For clips of every LED state, see Breaker LED states · video reference.
Connectivity
Controller appears in Hybird OS with recent "last seen"
Connection type (Ethernet/Wi-Fi/LTE) as intended
Breaker discovery
Breaker scan shows all installed breakers
All Modbus IDs unique
No missing devices
Data verification
Each breaker shows: voltage, current, power, leakage, temperature, state
Three-phase breakers show per-phase data
Voltage in expected range (\~230V single-phase)
Leakage at normal levels (below 5 mA typical)
Labelling
Every breaker labelled with descriptive circuit name in Hybird OS
Remote switching test
Test off/on via Hybird OS on one non-critical breaker
State change reflected within seconds
Breaker LED follows: blinking red when on, blinking blue when off
Customer handoff
Dashboard URL and credentials provided
Support contact shared: [email protected] / +45 3020 4900
Eloverblik consent process initiated or scheduled