Skip to main content

Hybird RCBO complete technical specifications

Product overview

The Hybird RCBO (Residual Current Operated Circuit Breaker) combines residual current protection with overcurrent protection in a single smart device. The RCBO is connected to the Hybird Edge Controller via RS485 Modbus, enabling real-time monitoring and remote state reporting.

Available configurations

RCBO 2P (Two-Pole)

Single-phase applications with neutral.

Amperage

Residual Current Sensitivity

Curve Type

6A, 10A, 13A, 16A

30mA, 100mA, 300mA

B, C

RCBO 4P (Four-Pole)

Three-phase applications with neutral.

Amperage

Residual Current Sensitivity

Curve Type

10A, 13A, 16A, 20A, 25A, 32A, 35A, 50A, 63A, 80A, 100A

30mA, 100mA, 300mA

B, C

C curve is standard stock. B curve is available made-to-order with approximately 4 weeks lead time.

Physical specifications

Specification

RCBO 2P

RCBO 4P

Height

109 mm

109 mm

Width

71 mm

107 mm

Depth

74 mm

73 mm

Weight

490 g

840 g

DIN rail mounting

Standard 35 mm DIN rail (EN 60715)

Standard 35 mm DIN rail (EN 60715)

Terminal type

Accepts conductor sizes appropriate to the connected cable

Accepts conductor sizes appropriate to the connected cable

Electrical ratings

Specification

Rating

Rated voltage (2P)

220–240 V AC

Rated voltage (4P)

380–415 V AC

Rated frequency

50 Hz

Rated breaking capacity

6 kA

Overvoltage category

Category III (IEC 60364)

Residual current protection

Specification

Details

Sensitivity options

30 mA, 100 mA, 300 mA

Trip threshold

Trips at the rated residual current (30 mA, 100 mA, or 300 mA depending on variant)

DC leakage detection

Type B capability available (detects AC, pulsating DC, and smooth DC leakage)

Curve types explained:

  • Type C (standard stock): General-purpose protection. Trips at 5–10 times rated current in instantaneous zone. Typical for conventional domestic and commercial installations.

  • Type B (made-to-order): Lower threshold. Trips at 3–5 times rated current in instantaneous zone. Suitable for circuits with minimal inrush current and for installations with variable frequency drives, IT equipment, or renewable energy systems.

Modbus communication

Each RCBO connects to the Edge Controller via RS485 Modbus RTU at 500 Kbps. Each device provides thousands of holding registers for measurement and state data. There are no input registers or coils.

Standards compliance

All Hybird RCBOs are CE and RoHS certified, covering both electromagnetic compatibility (EMC) and the Low Voltage Directive (LVD). Certificate copies are available on request from [email protected].

Model naming convention

Hybird RCBO model numbers follow this structure: HY-RCBO-[Curve][Amps][Config]-V[Version]

Example: HY-RCBO-C16C4P-V3 = Hybird RCBO, C curve, 16A, 4-pole, V3 firmware.

Further specifications

Trip times, thermal trip curves, environmental limits (operating temperature, humidity, IP rating), and recommended test intervals will be published in the updated datasheet. Contact [email protected] for the latest datasheet.


Need help?

Technical support: [email protected]
Billing and invoicing: [email protected]
Sales and partnerships: [email protected]
Phone: +45 3020 4900